| #32 Where is the Emissivity Adjustment? |
| In the readout device. |
|
| The normal setup and calibration as shown in the IRt/c Operating Manual and Tech Note #1 automatically compensates for the emissivity and reflectivity of the material whose temperature is being con-trolled, and completely accounts for these effects at the controlled temperature. However, for processes in which the control temperature set-point varies, the control device will provide higher accuracy over a wider range if its SPAN or GAIN adjustment is used to calibrate the process. Accordingly, the calibration set-up should include a standard two point method of setting the span. |
 |
Install IRt/c as close as possible. |
 |
Wire connections in standard fashion. |
 |
At low operating temperature, measure actual temperature with D-Series. |
 |
Adjust OFFSET, ZERO, or LO CAL to match reading on D-Series. |
 |
At high operating temperature, measure actual temperature with D-Series. |
 |
Adjust SPAN, GAIN, or HI CAL to match reading on D-Series. |
|
|
|
|
|
|
|